Description
INPUT
Voltage: (Jumper selectabe) 95-132V ac or 190-264V ac
Frequency: 50-60 Hz nominal
Phase: 1
OUTPUT
Voltage: max 90V dc at 207V ac input
Current: continuous 4 A dc | Intermittent 6 A for 10 secs
Resistance: 15 ohms minimum
REGULATION: +/- 1.0%
THERMAL DRIFT: 0.05% per deg. C change in AVR ambient
TYPICAL SYSTEM RESPONSE
Avr Response: 20ms
Filed Current to 90%: 80ms
Machine Volts to 97%: 300 ms
EXTERNAL VOLTAGE ADJUSTMENT: +/-10% with 1 k ohm 1 watt trimmer
UNDER FREQUENCY PROTECTION
Set Point: 95% Hz
Slope: 170% down to 30 Hz
UNIT POWER DISSIPATION: 10 watts maximum
BUILD UP VOLTAGE: 4 Volts @ AVR terminals
ENVIRONMENTAL
Vibration: 20-100 Hz 50mm/sec | 100Hz – 2kHz 3.3g
Operating Temperature: -40 to +70°C
Relative Humidity: 0-70°C 95%
Storage Temperature: -55 to +80°C
Reviews
There are no reviews yet.