Description
SENSING and POWER INPUT
Voltage: 100-264 V ac 1 phase
Frequency: 50-60 Hz nominal
OUTPUT
Voltage: 82 V d.c. @ 200 Va.c power input.
Voltage: 45 V d.c. @ 110 Va.c power input.
Current: Continuous 5A | transient 7.5A for 10 secs.
Resistance: 15 ohms min
REGULATION: +/- 1.0%
THERMAL DRIFT: 0.03% per deg. C change in AVR ambient (see note 3)
TYPICAL SYSTEM RESPONSE
AVR response: 20ms
Field current to 90%: 80 ms
Machine Volts to 97%: 300ms
EXTERNAL VOLTAGE ADJUSTMENT: +/-10% with 1 k ohm 1 watt trimmer
Increasing resistance lowers voltage.
Fixed 15kOhm resistor enables 110V sensing
UNDER FREQUENCY PROTECTION
Set point: 94-98% Hz
UNIT POWER DISSIPATION: 12 watts maximum
BUILD UP VOLTAGE: 4 Volts @ AVR terminals
QUADRATURE DROOP INPUT: 10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33 A
OVER EXCITATION PROTECTION
Set point: 67 Vdc +/-3% (fixed)
Time delay: 10-15 seconds (fixed)
ENVIRONMENTAL
Vibration: 20-100 Hz 50mm/sec | 100Hz – 2kHz 3.3g
Operating temperature: -40 to +70C
Relative Humidity: 0-70C 95%
Storage temperature: -55 to +80C
Reviews
There are no reviews yet.