– Detected voltage: 120 (90~132) or 240 (171~264) VAC, single phase two wire, chosen by toggle switch
– Frequency: 50/60Hz, chosen by connecting line
– Output voltage of magnetic field: max voltage 37VDC when input 120VAC, max voltage 74VDC when input 240VAC
– Continuous current: 4A
– Discontinuous current: 7A within 60s
– Resistance: Min 6Ω,Max 100Ω
– Voltage adjustment rate: < ±1% (the engine speed changed within 4%)
– Voltage build-up when the residual magnetism voltage of AVR input terminal is above 3.5VAC
– Outside voltage adjustment rate: ±5% (used 1KΩ, 1Watt potentiometer)
±10% (used 2KΩ, 1Watt potentiometer)
– Max consumed power: 8Watt
– EMI suppression circuit, with electromagnetic interference filter inside
– Under-frequency protection: the turning point of 60Hz system is 55Hz; the turning point of 50Hz system is 45Hz (the turning point set when it leaves the factory)
– Operation temperature: -40~60℃
– Storage temperature: -65~85℃
– Relative humidity: below 95%
– Vibration: 1.3G @ 5~26Hz, 5.0G @ 52~1000Hz
– Special turret:
VOLT: regulate voltage;
STAB: regulate stability
U/F: setting for under-frequency protection
– Dimension: 99.5×67.0×47.5 (L×W×H)
– Weight: 185g ±2%